Addressable Detectors and Sounders

 Addressable Detectors

The CQR 358 series of analogue addressable detectors have been designed to be fully compatible with the FireBrand addressable intelligent control panels, both for the FI/PN/A and FI/PN/A/NET range. The devices also have dual LED’s for 360° visibility giving easier identification of the device in fire or fault condition.

They are approved to EN54 part 5 and 7 and certified to DIFT for CPD complience.

Other features include advance detection and discrimination algorithms, easy installation and maintainence, sleek low-profile design and a durable sensor head.

FI/CQR358D-S-LED
FI/FB/358D-S-LED


 

This is a smoke detector which uses the scatter detection method, this means that smoke enters the chamber which in turn reflects a light source on to a receiver to generate an alarm condition.

  

Addressable Detectors FI/CQR/358-D-S-LED Technical Data
Smoke Sensitivity
0.09~0.14 d/B (EN 54)  0.10-0.14 dB/M (EN54)   
Ceiling Spacing N/A
CurrenyStart up Current 800mA (max)   
Standby Current   500uA (max) 
 Alarm Current   5mA (max) 
Remote LED Current
2mA 
 Start up Time 150mA to 24V, 10 ohm 0.25W resistor in series   30 Sec (max) 
Dimensions Dia: 100mm H: 46mm with base 
omplies with  Complies with  Complies with  Complies with   Weight   150g / set with base 
Operating Temperature  -10 to +50C 
Humidity 0 to 90% RH, non-condensing or icing  
Protection Category  IP42 
Ordering Information FI/CQR/358-D-S-LED23   

FI/CQR358D-H-LED
FI/FB/358D-H-L

 

This is a heat detector which has 2 methods of detection, Fixed temperature and Rate of Rise.

Addressable Detectors FI/CQR/358-D-H-LED Technical Data
Fixed Temperature
59°C

oC

 
Rate of Rise
3°C in 30seconds
CurrenyStart up Current 800uA (max)   
Standby Current   500uA (max) 
 Alarm Current   5mA (max) 
Remote LED Current
2mA 
 Start up Time 150mA to 24V, 10 ohm 0.25W resistor in series   30 Sec (max) 
Dimensions Dia: 100mm H: 60mm
omplies with  Complies with  Complies with  Complies with   Weight   150g / set with base 
Operating Temperature  -10 to +50C 
Humidity 0 to 90% RH, non-condensing or icing  
Protection Category  IP42 
Ordering Information FI/CQR/358-D-H-LED23   

FI/CQR358D-SH-LED
FI/FB/358D-SH-LED




This is a combined smoke and heat detector which incorporates all detection methods that are used in the individual detector.


Addressable Detectors FI/CQR358D-SH-LED - Technical Data
Smoke Sensitivity
0.09~0.14 d/B (EN 54)  0.10-0.14 dB/M (EN54)   
Fixed Temperature
59°C
Rate of Rise 30 30°C in 30seconds
CurrenyStart up Current 800uA (max)   
Standby Current   500uA (max) 
 Alarm Current   4mA 
Remote LED Current
2mA 
 Start up Time 150mA to 24V, 10 ohm 0.25W resistor in series   30 Sec (max) 
Dimensions Dia: 100mm H: 60mm 
omplies with  Complies with  Complies with  Complies with   Weight   150g / set with base 
Operating Temperature  -10 to +50C 
Humidity 0 to 90% RH, non-condensing or icing  
Protection Category  IP42 
Ordering Information FI/CQR/358-D-SH-LED23   

FP3/RD/ADD